January 2023
23
What happened?
Between 15:39 UTC and 19:38 UTC on 23 January 2023, a subset of customers in the South Central US region may have experienced increased latency and/or intermittent connectivity issues while accessing services hosted in the region. Downstream services that were impacted by this intermittent networking issue included Azure App Services, Azure Cosmos DB, Azure IoT Hub, and Azure SQL DB.
What went wrong and why?
The Regional Network Gateway (RNG) in the South Central US region serves network traffic between Availability Zones, which includes datacenters in South Central US and network traffic in and out of the region. During this incident, a single router in the RNG experienced a hardware fault, causing a fraction of network packets to be dropped. Customers may have experienced intermittent connectivity errors and/or error notifications when accessing resources hosted in this region.
How did we respond?
The Azure network design includes extensive redundancy such that, when a router fails, only a small fraction of the traffic through the network is impacted - and automated mitigation systems can restore full functionality by removing failed any routers from service. In this incident, there was a delay with our automated systems in detecting the hardware failure on the router, as there was no previously known signature for this specific hardware fault. Our synthetic probe-based monitoring fired an alert at 17:58 UTC, which helped to narrow down the potential causal location to the RNG. After further investigation we were able to pinpoint the offending router, but it took additional time to isolate because the failure made the router inaccessible via its management interfaces. The unhealthy router was isolated and removed from service at 19:38 UTC, which mitigated the incident.
How are we making incidents like this less likely or less impactful?
- We are implementing improvements to our standard operating procedures for this class of incident to help mitigate similar issues more quickly (Estimated completion: February 2023).
- We are implementing additional automated mitigation mechanisms to help identify and isolate such unhealthy routers more quickly in the future (Estimated completion: May 2023).
- We are still investigating the cause of the hardware fault and are collaborating weekly with the hardware vendor to diagnose this unknown OS/hardware failure and obtain deterministic repair actions.
How can we make our incident communications more useful?
You can rate this PIR and provide any feedback using our quick 3-question survey: https://aka.ms/AzPIR/7NBR-T98