June 2022
7
What happened?
Between 02:41 and 14:30 UTC on 07 Jun 2022, a subset of customers experienced difficulties connecting to resources hosted in one particular Availability Zone (AZ) of the East US 2 region. This issue impacted a subset of storage and compute resources within one of the region’s three Availability Zones. As a result, Azure services with dependencies on resources in this zone also experienced impact.
Since the vast majority of services that were impacted already support Availability Zones customers using always-available and/or zone-redundant services would have observed that this zone-specific incident did not affect the availability of their data and services. Five services (Application Insights, Log Analytics, Managed Identity Service, Media Services, and NetApp Files) experienced regional impact as a result of this zonal issue. These five services are already working towards enabling AZ support. Finally, while App Service instances configured to be zone-redundant would have stayed available, from the other AZs, control plane issues were observed regionally that may have prevented customers from performing service management operations during the impact window.
What went wrong, and why?
Microsoft experienced an unplanned power oscillation in one of our datacenters within one of our Availability Zones in the East US 2 region. Components of our redundant power system created unexpected electrical transients, which resulted in the Air Handling Units (AHUs) detecting a potential fault, and therefore shutting themselves down pending a manual reset.
The electrical transients were introduced by anomalous component behavior within Uninterruptible Power Supply (UPS) modules, and cascaded throughout the datacenter electrical distribution system including electrical power supply to the mechanical cooling plant. As a result of the AHU self-protective shutdown, cooling to the datacenter was interrupted. Although the electrical transients did not impact our compute, networking, or storage infrastructure – which did not lose power – the mechanical cooling plant shutdown led to an escalating thermal environment, which induced protective shutdown of a subset of this IT infrastructure prior to the restoration of cooling.
Thorough detailed analysis has resulted in an adjustment to the UPS gain settings, preventing any further oscillations. These oscillations are the power equivalent of having a microphone too close to an amplifier – just as setting the volume too high can trigger a self-sustained sound oscillation, power oscillations can occur when the gain of the UPS is too high. The normal process of adding load to the UPS units results in an increase in gain and, in this case, the gain went high enough to cause the oscillations to occur. Adjusting the control gain setting lower in the UPS returns them to stable operation for all load values, preventing disruptions to any other infrastructure such as the AHUs.
Subsets of equipment including network, storage, and compute infrastructure were automatically shut down, both to prevent damage to hardware and to protect data durability under abnormal temperatures. As a result, Azure resources and services with dependencies on these underlying resources experienced availability issues during the impact window. A significant factor of downstream service impact was that our storage infrastructure was amongst the hardware most affected by these automated power and thermal shutdowns. Eight storage scale units were significantly impacted – due to thermal shutdowns directly and/or loss of networking connectivity, itself due to thermal shutdowns of corresponding networking equipment. These scale units hosted Standard Storage including LRS/GRS redundant storage accounts, which in turn affected Virtual Machines (VMs) using Standard HDD disks backed by this storage, as well as other services and customers directly consuming blob/file and other storage APIs.
The platform continuously monitors input/output transactions from the VMs to their corresponding storage. So even if the scale unit running a VM’s underlying compute was operational, when transactions did not complete successfully within 120 seconds (inclusive of retries) the connectivity to its virtual disk is considered to be lost, and a temporary VM shutdown is initiated. Any workloads running on these impacted VMs, including first-party Azure services and third-party customer services, would have been impacted as their underlying hosts were either shut down by thermal triggers, or had their storage/networking impacted by the same.
How did we respond?
As soon as the AHUs shut themselves down as a result of the power disturbance, alerts notified our onsite datacenter operators. We deployed a team to investigate, who confirmed that the cooling units had shut themselves down pending manual intervention. Following our Standard Operating Procedure (SOP), the team attempted to perform manual resets on the AHUs, but these were not successful. Upon further investigation the onsite team identified that, due to the nature of this disturbance, recovering safely would require resetting the AHUs while running on backup power sources, to prevent the power oscillation pattern on the utility line from triggering a fault. This meant that two primary steps were required to recover – firstly, the impacted datacenter manually transferred from utility power to backup power sources, our onsite generators. By doing this, we changed the characteristics in the power lineup to obviate the creation of the oscillations. Secondly, the AHUs were then manually reset to recover them, which restored cooling to the datacenter.
Once temperatures returned to normal levels, some hardware including network switches needed to be manually power cycled to be brought back online. The network hardware and components serve different compute and storage resources for the scale units in this datacenter, including host instances for other applications and services. Onsite engineers then manually reviewed the status of various infrastructure components, to ensure that everything was working as intended.
Following the restoration of most storage network connectivity, recovery activities included diagnosing and remediating any host nodes that had entered an unhealthy state due to loss of network, and triaging any other hardware failures to ensure that all storage infrastructure could be brought back online. Even after all storage nodes returned to a healthy state, two storage scale units still exhibited slightly lower API availability compared to before this incident. It was determined that this was caused by a limited number of storage software roles being in an unhealthy state – those roles were restarted, which restored full API availability for those scale units.
Since our compute continuously monitors for Storage access, as storage/networking started recovering the compute VMs automatically started coming back up. This worked as expected in all cases expect on one scale unit, where the physical machines were shut down and did not recovery automatically. Since the VMs were originally down due to storage/networking issues, it was only detected once storage recovered, so we manually recycled the nodes to bring them back online. Upon investigation, an issue with the cluster power management unit prevented automatic recovery.
Two specific Azure services (ExpressRoute and Spatial Anchors) performed manual mitigations to fail customers over to use the other two Availability Zones within the region. Thus, while some impacted services recovered even earlier, full mitigation of this incident was declared at 14:30 UTC.
After cooling was restored and infrastructure was brought back online, our onsite teams opted to leave the datacenter running on backup power sources during additional investigations and testing, both focused on the UPS gain setting. In consultation with our critical environment hardware suppliers, we ran comprehensive testing to confirm the relevant gain settings based on the amount of load across the system. After these settings were deployed, we have since returned the datacenter back to our normal utility power feed.
How are we making incidents like this less likely or less impactful?
Already completed:
- Updates to the gain setting, described above, have been deployed and the datacenter is back on utility in the impacted datacenter. We are confident that this has mitigated the risk of the power oscillation issue that was triggered.
- Furthermore, our critical environment team has assessed systemic risk across all our datacenters globally, to ensure that none are at risk of the same situation. Of our 200+ Azure datacenters across 60+ regions, we identified only one other datacenter (beyond the impacted datacenter in East US 2) that had a similar power draw that could have potentially triggered a similar oscillation – this risk has since been mitigated with a similar configuration change.
Work in progress:
- We have identified opportunities to improve our tooling and processes to flag anomalies more quickly, and are in the process of fine-tuning our alerting to inform onsite datacenter operators more comprehensively.
- We are investigating why a subset of networking switches took longer than expected to recover. Although these were manually mitigated during the incident, we are exploring ways to optimize this recovery to ensure that customer workloads are brought online more quickly.
- Similarly, we continue to diagnose a small subset of storage and compute nodes that remained in unhealthy states after restoration of networking, to streamline their recovery. This includes addressing a driver-related issue that prevented compute nodes in one scale unit from recovery automatically.
- We are addressing some specific monitoring gaps including for compute nodes that have not been powered back on, specifically for scenarios in which they had been automatically shut down.
In the longer term:
- We are developing a plan for fault injection testing relevant critical environment systems, in partnership with our industry partners, to be even more proactive in identifying and remediating potential risks.
- We are exploring improved supplier diversity in the critical environment space, to minimize potential single points of failure within our hardware lineup.
- We are investing in improved engineering tooling and processes that will accelerate the identification and remediation of unhealthy node states during incidents of this scale.
- We have several workstreams in motion that will further improve storage node start-up times, learnings from this incident have validated the need to prioritize these optimizations.
- Finally, we continue to invest in expanding how many Azure services support Availability Zones, so that customers can opt for automatic replication and/or architect their own resiliency across services: https://docs.microsoft.com/azure/availability-zones/az-region
How can our customers and partners make incidents like this less impactful?
- Consider using Availability Zones (AZs) to run your services across physically separate locations within an Azure region. To help services be more resilient to datacenter-level failures like this one, each AZ provides independent power, networking, and cooling. Many Azure services support zonal, zone-redundant, and/or always-available configurations: https://docs.microsoft.com/azure/availability-zones/az-overview
- Consider which are the right Storage redundancy options for your critical applications. Zone redundant storage (ZRS) remains available throughout a zone localized failure, like in this incident. Geo-redundant storage (GRS) enables account level failover in case the primary region endpoint becomes unavailable: https://docs.microsoft.com/azure/storage/common/storage-redundancy
- Consider using Azure Chaos Studio to recreate the symptoms of this incident as part of a chaos experiment, to validate the resilience of your Azure applications. Our library of faults includes VM shutdown, network block, and AKS faults that can help to recreate some of the connection difficulties experienced during this outage – for example, by targeting all resources within a single Availability Zone: https://docs.microsoft.com/azure/chaos-studio
- More generally, consider evaluating the reliability of each of your critical Azure applications using guidance from the Azure Well-Architected Framework and its interactive Well-Architected Review: https://docs.microsoft.com/azure/architecture/framework/resiliency
- Finally, ensure that the right people in your organization will be notified about any future service issues - by configuring Azure Service Health alerts. These can trigger emails, SMS, push notifications, web-hooks, and more: https://aka.ms/ash-alerts